Product Introduction ACD-2KL is a automatic control instrument with sight display alarm and control functions. Using relay contact output alarm you can set the upper and lower limit alarm and back difference then drives a relay output.

Model:

Category:

+86-29-86687167

Product Introduction
ACD-2KL is a automatic control instrument with sight display, alarm and control functions. Using relay contact output alarm, you can set the upper and lower limit alarm and back difference , then drives a relay output. Signal isolation design, eliminate interference. Its advantages of high control precision, fast response, stable operation, small size, convenient installation , makes it an ideal substitute for electrical contact instrument.

 

 
  Product Patent
Utility model patent certificate
  ①ZL200820028605.1  《Buttons and LCD display of digital instrument》
 
  ②ZL200920062360.9  《Constant current driving circuit with micro power consumption low voltage drop sensor》
 
Appearance design patent certificate
  ①ZL200830019531.0 《Instrument (Pressure Testing Gauge)》
 
 
 Application
  - For the level measure of well, pond, water tower, etc;
  - For the level measure and monitoring of water conservancy and hydropower;
  - Water level measurement of urban water supply and sewage treatment;
- Liquid level measurement and control in industrial field;
- Liquid level measuring for all kinds of open tank, water tank and liquid tank;
 
  Characteristics
  - Support liquid density modification, can be directly measured in different media;
  - Acquisition speed (0.1~10)S/A, settable freely;
  - RS485 communication , (4~20)mA、(1~5)V output are available for choice;
  - Upper , lower limit relay, output independently;
  - Buttons pressed with magnetic induction pen, exempt from interference, not easy to damage;
  - Visual Level percentage bar chart display, easy to understand;
  - Signal isolation technology, anti electromagnetic, frequency interference technology, to ensure that the data is correct;
  - Zero Self-Stability technology, with temperature compensation automatically, stability reliable;
 
 Product Parameters
  Measure Range
  0~1mH2O~200mH2O    ( any scope within it )


  Accuracy
  0.05%F.S  、  0.1%F.S   、   0.2%F.S   、    0.5%F.S

  Output Signal   
  (4~20)mA(24V DC,three wire)

  Communication   
  RS485 

  Range Migration   
  Suggested not over load than  3:1 ( to the electrical current output signals )

Relay node capacity
  240VAC/1A、30VDC/2A

  Power Supply   
  External:(10~30)V DC

  Acquisition Speed
  (0.1~10)S/A,default is 0.25S/A,(S=second, A=acquisition) , time is settable,

  Stability
  Superior to 0.1%FS/Year

  Environmental Temperature
  (-30~70)℃  

  Relative Humidity
  <90%

  Atmospheric Pressure
  (86~106)kPa

  Others
  Correction reference environment temperature: :20℃±2℃
  When 0.05%F.S , the gauge environment temperature :(0~50)℃  

  The Medium temperature
  Normal (-40~120)℃
  Wide Temperature(-60~150)℃


  Display
  5 digits LCD + percentage bar chart

  Protection Grade
  IP65

  Explosion Proof Grade
  ExiaIICT4 Ga 
 
  Over Load Pressure
  (1.5~3) times of the measure range, depends on the measure range
 
  Software
    AncnView-T analysis software ( with USB communication), can Export instrument data, automatic storage, automatic drawing temperature curve, can be exported to Excel form, read, print, 